Main Switchboard

Contactor Panel are manufactured according to ISO 9001:2008 standards and meets IEC standards 62271-200. Panel are designed not affected by the external conditions, thus can be used in harsh conditions such as mining, oil and gas. There are various kinds of control panels such as the engine, fixed, removable....

Ứng dụng

Features

* Modular structure can be extended.

* Divide between compartments in the cabinet and the module with the metal plate.

* Glossary natural ventilation or forced to commit suicide compensation.

* Access panel : The door panels can either lift to reach in front or behind.

* All metal surfaces are clean grease and dirt by chemicals ( acids ) and water several times before painting and final treatment with phosphate and fixatives to protect against corrosion, stable to ensure that high adhesion.These parts are painted with powder coating at temperatures 200 ° C for 10 minutes to ensure the hardness of the paint surface.

* Form: Form 1 to form 4b

* Degree of protection: IP32 to IP 54

* Ambient temperature: from -50 ° C up to + 40 ° C (average of 24 hours must not exceed + 40 ° C) 

* Altitude: Up to 2000m

* Relative Humidity: Maximum temperature. +40 ° C, ≤ 50% 
                                 Nhiệt độ. + 20°C;  ≤ 95 %

Parameters

Reference standard

IEC 61439-1/2

Class of protection

IEC 60529

Installation

In House

Rated isolation voltage (Ui)

1000V

Rated operating voltage (Ue)

415/690 V AC

Rated frequency (F)

50 / 60 Hz

Rated impulse voltage  (Uimp)

8 kV

Rated auxiliary circuit voltage

230 V AC max

Degree of pollution

3

Rated current (In)

4000 A

Electric current vertical busbar

4000 A

Rated short-time current (ICW) 3s

Horizontal busbar

65 kA rms

Vertical busbar

65 kA rms

Rated peak current

143 kA

Earthing diagram

TNC

Current limit of power incoming and outcoming feeders

4000 A

Power limit of motor control feeders

Up to 250 kW 415/690 V

Dimensions


 

SIZE
Height (H) 2000/2200/2400
Width (W) 600/700/800/900/1000/1200
Depth (D) 600/800/1000/1200/1400/1600